Pool Heat Pumps
AstralPool Proheat II Standard/Chiller, Heat Pump.
AstralPool Proheat II Standard/Chiller is a family of industrial heat pumps that heat large facility pools. Çilek Havuz supplies Proheat II Standard · Chiller through quotes and as part of its projects. The Standard version heats only; the Chiller version provides automatic cooling in addition to heating. Each version comes in five capacity steps. The Standard models deliver 36.2 kW to 125.5 kW of heating at 25°C air and 26°C water. The supply is 400 V three-phase.
CH-ISI-0017-01

- Heating Output
- 36.2-125.5kW
- Version
- Standard (heating) or Chiller (heating and cooling)
- List price
- From €22,050 + VAT
Prices are list prices dated 16.06.2026, excluding VAT.
Suitable pool and installation
Models and price
10 models
List price €22,050 - €73,500 excl. VAT
Lowest list price: Proheat II 35 - Standard
List price, excluding VAT. The final figure depends on quantity and scope and is given in the quotation.
See all models and technical dataCompatibility and connections
- Version
- Standard (heating) or Chiller (heating and cooling)
- Power supply
- 400 V, 3 phase, 50 Hz
- Water flow
- 12-70 m³/h, depending on step
- Line connection
- 63 mm (35, 45, 60), 75 mm (90, 120)
- Minimum air temperature
- 0°C
// Models
AstralPool Proheat II Standard/Chiller models, with list prices and technical data.
10 products
Proheat II 35 - Standard
RecommendedCode CH-ISI-0017-01
- Heating Output
- 36.2 kW
- Flow Rate
- 12 - 15 m³/h
Price€22,050 + VAT- Manufacturer Code
- 65542-MOB
- Type
- Standard
- Heating Output
- 36.2 kW
- Power input
- 6.4 kW
- COP (Efficiency)
- 5.7
- Heating capacity (air 15°C)
- 30.5 kW
- Power input (air 15°C)
- 6.2 kW
- COP (air 15°C)
- 4.9
- Heating capacity (air 5°C)
- 23.2 kW
- Power input (air 5°C)
- 6.0 kW
- COP (air 5°C)
- 3.9
- Cooling capacity
- -
- Cooling power input
- -
- EER (cooling efficiency)
- -
- Cooling capacity (air 43°C)
- -
- Cooling power input (air 43°C)
- -
- EER (air 43°C)
- -
- Flow Rate
- 12 - 15 m³/h
- Connection
- 63 mm
- Power Supply
- 400 V
- Phase
- 3
- Frequency
- 50 Hz
- Current
- 13.75 A
- Max. current
- 23.4 A
- Recommended supply cable cross-section (mm²)
- 4
- Refrigerant
- R410A
- Refrigerant charge
- 4 kg
- Number of fans
- 1
- Sound level
- 66.2 dBA
- Sound pressure (5 m)
- 60.9 dBA
- Material
- Magnesium-coated aluminium casing, G2 titanium heat exchanger
- Min. operating air temperature
- 0 °C
Proheat II 45 - Standard
Code CH-ISI-0017-02
- Heating Output
- 44.4 kW
- Flow Rate
- 15 - 25 m³/h
Price€27,825 + VATProheat II 60 - Standard
Code CH-ISI-0017-03
- Heating Output
- 63.5 kW
- Flow Rate
- 25 - 35 m³/h
Price€33,600 + VATProheat II 90 - Standard
Code CH-ISI-0017-04
- Heating Output
- 91.3 kW
- Flow Rate
- 30 - 50 m³/h
Price€54,600 + VATProheat II 120 - Standard
Code CH-ISI-0017-05
- Heating Output
- 125.5 kW
- Flow Rate
- 50 - 70 m³/h
Price€55,650 + VATProheat II 35 - Chiller (heating + cooling)
Code CH-ISI-0017-06
- Cooling capacity
- 42.3 kW
- Flow Rate
- 12 - 15 m³/h
Price€32,550 + VATProheat II 45 - Chiller (heating + cooling)
Code CH-ISI-0017-07
- Cooling capacity
- 51.0 kW
- Flow Rate
- 15 - 25 m³/h
Price€34,650 + VATProheat II 60 - Chiller (heating + cooling)
Code CH-ISI-0017-08
- Cooling capacity
- 72.0 kW
- Flow Rate
- 25 - 35 m³/h
Price€40,950 + VATProheat II 90 - Chiller (heating + cooling)
Code CH-ISI-0017-09
- Cooling capacity
- 104.0 kW
- Flow Rate
- 30 - 50 m³/h
Price€60,900 + VATProheat II 120 - Chiller (heating + cooling)
Code CH-ISI-0017-10
- Cooling capacity
- 140.0 kW
- Flow Rate
- 50 - 70 m³/h
Price€73,500 + VAT
// 01 · Technical table
AstralPool Proheat II Standard/Chiller technical values
Where a value changes from model to model, every option is listed in that row; the details for each model are in the model list below.
| Specification | Value |
|---|---|
| Manufacturer Code | 65542-MOB / 65543-MOB / 65544-MOB / 65545-MOB / 65546-MOB / 68245-MOB / 68246-MOB / 68247-MOB / 68248-MOB / 68249-MOB |
| Type | Standard / Chiller (heating + cooling) |
| Heating Output | 36.2 kW / 44.4 kW / 63.5 kW / 91.3 kW / 125.5 kW (on some models) |
| Power input | 6.4 kW / 8.2 kW / 11.9 kW / 17.0 kW / 24.3 kW (on some models) |
| COP (Efficiency) | 5.7 / 5.4 / 5.3 / 5.2 (on some models) |
| Heating capacity (air 15°C) | 30.5 kW / 39.7 kW / 56.8 kW / 80.2 kW / 110.5 kW (on some models) |
| Power input (air 15°C) | 6.2 kW / 8.1 kW / 11.5 kW / 16.8 kW / 23.9 kW (on some models) |
| COP (air 15°C) | 4.9 / 4.8 / 4.6 (on some models) |
| Heating capacity (air 5°C) | 23.2 kW / 30.0 kW / 41.3 kW / 61.0 kW / 80.1 kW (on some models) |
| Power input (air 5°C) | 6.0 kW / 7.9 kW / 10.7 kW / 16.2 kW / 22.7 kW (on some models) |
| COP (air 5°C) | 3.9 / 3.8 / 3.5 (on some models) |
| Cooling capacity | 42.3 kW / 51.0 kW / 72.0 kW / 104.0 kW / 140.0 kW (on some models) |
| Cooling power input | 7.0 kW / 8.4 kW / 12.0 kW / 17.3 kW / 24.4 kW (on some models) |
| EER (cooling efficiency) | 6.0 / 6.1 / 5.7 (on some models) |
| Cooling capacity (air 43°C) | 29.1 kW / 37.0 kW / 49.5 kW / 74.0 kW / 99.0 kW (on some models) |
| Cooling power input (air 43°C) | 9.4 kW / 11.9 kW / 15.6 kW / 24.5 kW / 31.2 kW (on some models) |
| EER (air 43°C) | 3.1 / 3.2 / 3.0 (on some models) |
| Flow Rate | 12 - 15 m³/h / 15 - 25 m³/h / 25 - 35 m³/h / 30 - 50 m³/h / 50 - 70 m³/h |
| Connection | 63 mm / 75 mm |
| Power Supply | 400 V |
| Phase | 3 |
| Frequency | 50 Hz |
| Current | 13.75 A / 17.1 A / 25.1 A / 33 A / 45.4 A / 13.14 A / 24.2 A / 31.5 A / 43.7 A |
| Max. current | 23.4 A / 29.8 A / 39.8 A / 63.6 A / 79.6 A |
| Recommended supply cable cross-section (mm²) | 4 / 6 / 10 / 16 / 25 |
| Refrigerant | R410A |
| Refrigerant charge | 4 kg / 6 kg / 9 kg / 2 x 6.5 kg / 2 x 9 kg |
| Number of fans | 1 / 2 |
| Sound level | 66.2 dBA / 72.5 dBA / 71.1 dBA |
| Sound pressure (5 m) | 60.9 dBA / 68.4 dBA / 69.4 dBA |
| Material | Magnesium-coated aluminium casing, G2 titanium heat exchanger |
| Min. operating air temperature | 0 °C |
// 02 · Use
Users and applications
Proheat II Standard/Chiller is intended for facilities with large pools, such as hotels. A facility that only wants to extend the season or heat in winter chooses the Standard version. The Chiller version is chosen in hot climates where the water overheats in summer, or for a pool where a constant temperature is wanted all year round. Both versions are compatible with remote connection (Fluidra Connect).
- Hotel and large facility pools
- Hot climate facilities where the water needs cooling in summer (Chiller)
- Season extension projects that need heating only (Standard)
- Pools with a 400 V three-phase supply needing more than 36.2 kW of heat
// 03 · Installation and compatibility
Installation and compatible equipment
The unit is connected to the pool line after the filter; the connection is 63 mm on steps 35, 45 and 60 and 75 mm on steps 90 and 120. The supply is 400 V three-phase, and the maximum current is between 23.4 A and 79.6 A. Steps 90 and 120 carry two fans. The area in front of the fan outlets is kept clear, and space is left around the unit for servicing.
- The version is chosen first: Standard for heating only, Chiller if cooling is also needed.
- The capacity step is determined according to winter and summer demand.
- The unit is placed with the fan outlet left clear.
- The water line is connected at 63 or 75 mm after the filter.
- The 400 V three-phase supply is run according to the maximum current.
// 04 · Maintenance
Maintenance checkpoints
The main maintenance task is keeping the air coil and fans clean. If leaves and dust block the coil, heating and cooling output falls. The pH and hardness of the pool water are kept in balance, and the water flow is monitored within the range of the step. On the Chiller version, the switch between heating and cooling is tested at the start of the season. The R410A circuit is opened only by an authorised service.
- The air coil and fans are cleaned at the start of the season.
- The water flow is kept within the range of the step (12-70 m³/h).
- On the Chiller version, the mode switch is checked at the start of the season.
- Only an authorised service works on the R410A circuit.
// 05 · Information form
Request information on this product
Leave your name and contact details, and your customer representative will get back to you about the models of this product, its fit for your pool and an up-to-date quote.

Subject of the form
AstralPool Proheat II Standard/Chiller
- Product
- AstralPool Proheat II Standard/Chiller
- Category
- Pool Heating Systems
- Number of models
- 10
- Code
- CH-ISI-0017-01 ... CH-ISI-0017-10
Your request is recorded under the name of this product. If you prefer not to wait, you can also reach us on +90 216 475 39 37.
Your contact details
Name, surname, phone and email are enough.
// 06 · Reviews
AstralPool Proheat II Standard/Chiller reviews
If you use this product or have used our service for it, share your experience. Every review is published after our team verifies it, and ratings are calculated from verified reviews only.
Average rating
0/5
Verified reviews: 0
- 5 out of 5 stars
- 0
- 4 out of 5 stars
- 0
- 3 out of 5 stars
- 0
- 2 out of 5 stars
- 0
- 1 out of 5 stars
- 0
Reviews are verified and published by the Çilek Havuz team. A product review covers the product itself; a service review covers delivery, installation and communication.
There are no verified reviews for this product yet. Be the first to write one.
Write a review// 07 · Related products
Products considered together
First the products in the same family, then the power, connection and control parts it needs to run, and finally the complementary products usually chosen with it.
// 08 · Services
Work carried out with this product
AstralPool Proheat II Standard/Chiller can be purchased on its own or installed as part of a pool construction or maintenance project.
- Swimming Pool ConstructionReinforced-concrete, prefabricated and infinity swimming pools, built turnkey for villa, residential and commercial projects.
- Thermal PoolsDurable pool systems built for thermal water.
- Infinity PoolsPools that open onto the view, with water spilling over the edge into a balance tank.
- Pool MaintenanceWater chemistry, equipment and periodic maintenance.
// 09 · Guides
Selection and installation guides
These articles cover the calculations, comparisons and installation details considered when choosing and installing AstralPool Proheat II Standard/Chiller.
// 10 · Data sheet and catalogue
Printable documents
The technical data sheet is a single A4 page. The product catalogue brings together the cover, images, model list and technical table.
- Product details
- AstralPool Proheat II Standard/Chiller
- Model
- 10
- Code
- CH-ISI-0017-01 - CH-ISI-0017-10
- Category
- Pool Heating Systems
// 11 · Design and catalogues
Set up your project on screen first, then review the products in our catalogues.
In the design studio you can build your space with its materials and colours; in the product catalogues you can see models, technical sheets and list prices.
PoolDesign studio
Build your pool, sauna, steam room or Turkish hammam on screen with lining, timber and marble options, then request a quote with your selection.
Where would you like to start?
Product catalogues
Models, technical sheets and list prices of our product groups are on the category pages.
Next step
Let us discuss your project in the way that suits you best.
You can fill in the form for a written quote, schedule a video project presentation or ask us to survey your project site.
Get a Quote
Send us your dimensions and expectations in writing.
Online presentation
Video project presentation
On-site survey
Inspection at your project site
// 12 · Company & Contact
To talk about your project, call or write to us.
Legal Name
Çilek Havuz
Founded
1998 · Istanbul
Head Office
Çilek Plaza, Eyüp Sultan Mah. Yakacık Cd. Feshane Cd. No: 2 D:4 D:1, 34885 Sancaktepe / İstanbul
Service Area
All of Türkiye · exports to 14 countries
Branches
Kyrgyzstan · Egypt · Algeria · Iraq
Showroom
Plan a showroom visit
At our showroom in Çilek Plaza, Sancaktepe, you can discuss your project with our team. We recommend booking an appointment by phone before your visit.
Working Hours
- Monday – Friday · 08:00 – 17:30
- Saturday · 08:00 – 12:30
- Closed on Sunday
Questions
About AstralPool Proheat II Standard/Chiller: frequently asked questions
Çilek Havuz Corporate
Pool & Wellness Engineering
- Response Time
- Same day
- Channels
- Phone · Email · WhatsApp
If the answer you are looking for is not here, send your question directly to us and our team will reply as soon as possible.
+90 216 475 39 37Proheat II Standard only heats the pool water. Proheat II Chiller has an automatic cooling mode in addition to heating and cools the water in summer. Both versions come in the same steps 35, 45, 60, 90 and 120, with the same water flow and connection sizes. A facility that needs cooling chooses the Chiller version.
Çilek Havuz Corporate
At 30°C air and 26°C water, Proheat II Chiller delivers 42.3 kW to 140 kW of cooling. Under these conditions the EER is between 5.7 and 6.1. At 43°C air and 32°C water, cooling drops to between 29.1 kW and 99 kW, while the EER stays between 3.0 and 3.2.
Çilek Havuz Corporate
At 5°C air and 26°C water, Proheat II Standard delivers 23.2 kW to 80.1 kW of heating. Under the same conditions the COP is between 3.5 and 3.9. At 15°C air, output rises to between 30.5 kW and 110.5 kW. As the minimum operating air temperature is 0°C, winter capacity is assessed separately in cold regions.
Çilek Havuz Corporate
The step names and the 0°C lower limit are the same in both families. AstralPool Proheat II Indoor is installed in a plant room with a duct-connected centrifugal fan and operates at a noise level of 59.2 dBA to 61.5 dBA. On Standard/Chiller the noise level is between 66.2 dBA and 72.5 dBA. The Indoor family has no version with cooling. At 25°C air, Standard 35 delivers 36.2 kW and Indoor-35 43.6 kW.
Çilek Havuz Corporate
A three-phase 400 V supply is required; Proheat II Standard/Chiller does not run on single-phase. The rated current is 13.75 A on the Standard 35 step and 45.4 A on the Standard 120 step. The maximum current is between 23.4 A and 79.6 A. The cable section is given separately for each step; the panel and fuse are selected according to the maximum current.
Çilek Havuz Corporate
Sound power is 66.2 dBA on steps 35 and 45, 72.5 dBA on step 60, and 71.1 dBA on steps 90 and 120. Sound pressure at five metres is between 60.9 dBA and 69.4 dBA. For a plant room installation that needs a lower noise level, the ducted Proheat II Indoor is considered; the Indoor family stays between 59.2 dBA and 61.5 dBA.
Çilek Havuz Corporate
The COP value is 5.7 on step 35 and 5.2 on step 120; it is measured at 25°C air and 26°C water. At 15°C air the COP drops to between 4.6 and 4.9, and at 5°C air to between 3.5 and 3.9. Efficiency falls as the outdoor air gets colder; the model is selected according to the coldest operating month of the facility.
Çilek Havuz Corporate